Application

SKUM NFF 3x3 UL201 Foam Concentrate is intended for use on both types of Class B fires: hydrocarbon fuels with low water solubility (crude oils, gasolines, diesel fuels, aviation fuels) and polar solvent fuels with appreciable water solubility (methyl and ethyl alcohol, acetone, methyl ethyl ketone). It may also be used in conjunction with dry chemical agents to provide even greater fire suppression performance.

It is well-suited for municipal and industrial response to spills and limited-scale Type III hazards, as well as for foam systems equipped with Type II discharge devices. Typical applications include:

  • Industrial chemical and petroleum processing facilities
  • Truck/rail loading and unloading facilities
  • Flammable liquid containment areas
  • Mobile equipment fire protection

Minimum Recommended Application Rates

Fuel Group Concentration Lpm/m² Application Type
Hydrocarbons 3% 6.5 Type III – UL Listed
E15 3% 6.9 Type III – UL Listed
Hydrocarbons 3% 4.1 Type III – Third‐Party Witnessed
Premium Gasoline 3% 6.5 Type III – Third‐Party Witnessed
Hydrocarbons 3% 4.1 Type II – UL Listed
Alcohols 3% 6.9 Type II – UL Listed
Ethanol (EtOH) 3% 4.1 Type II – UL Listed
Ketones 3% 6.9 Type II – UL Listed
E85 3% 6.1 Type II – UL Listed

(1) TYPE III DISCHARGE OUTLET – A device that delivers foam directly onto the burning liquid as described in UL 162.
(2) NFPA 11 allows a design rate of 4.1 Lpm/m² for spill fire applications; this product has been tested per UL 162 for use at that rate.
(3) TYPE II DISCHARGE OUTLET – A device that delivers foam onto the burning liquid, partially submerges it, or produces restricted surface agitation as described in UL 162.